Variant 1: installed flush in a dropped/coffered ceiling
The TeamConnect Ceiling 2 can be easily installed in a dropped ceiling or coffered ceiling with square ceiling tiles (600 x 600 mm). Angle brackets are available for ceiling tiles with the standard dimensions of 2 ft or 625 mm.
When flush mounting, do not install the TeamConnect Ceiling 2 directly next to lights or other electrical devices in the ceiling.
WARNING | |
---|---|
A: secured with SL CM SK suspension kit

B: secured with eye bolts


B: secured with eye bolts
- Hand-tighten the M4x10 eye bolts in the TeamConnect Ceiling 2 to avoid damaging the metal housing by screwing them in too deeply.
-
Make sure that the thread on the eye bolt is fully within the thread at the mounting point.
Recommended cabling
Observe the following when connecting and running the cables:
- Always run the cables carefully and in a loop shape inside the installation recess.
- Make sure not to kink the cables to avoid breaking them or damaging the plugs.
Recommended paint protection measuresProtect the surface of your TeamConnect Ceiling 2 against scratches or damage to the paint by using the clear rubber feet included with delivery.
- On the underside of the TeamConnect Ceiling 2, clean the areas where you want to attach the feet.
- Attach the feet to the product.
Installing the TeamConnect Ceiling 2 without mounting bracket in the ceiling (600x600 mm grid):
- Remove a tile from the ceiling.
- Place the TeamConnect Ceiling 2 in the frame in the coffered ceiling.
-
Maintain the distances indicated in the figure.
Installing the TeamConnect Ceiling 2 with mounting brackets in the ceiling (2x2 ft or 625x625 mm grid):
-
Attach the mounting brackets to the TeamConnect Ceiling 2 as shown in the figure.
- Remove a tile from the ceiling.
- Place the TeamConnect Ceiling 2 in the frame in the coffered ceiling.
- Maintain the distances indicated in the figures.
-
Mounting with SL CM EB US:
-
Mounting with SL CM EB 625: